Power Systems: Introduction

A power system is the largest machine people have built. In a synchronous area such as Continental Europe, several hundred gigawatts of generators turn in step at 50 Hz50\ \text{Hz}, tied together by hundreds of thousands of kilometres of lines, and every second they must produce exactly what millions of loads consume plus the losses in between. Nothing stores the energy on the way: if a 1 GW1\ \text{GW} unit trips, the frequency starts to fall within milliseconds, and automatic controls in other power stations have seconds to make up the gap. This course shows how engineers calculate such a system: the voltages and currents in its three-phase networks, the power flows between its buses, the currents when something short-circuits, the relays that clear the fault, and the dynamics that decide whether the generators stay in step afterwards.

Safety rule for the whole course. Everything at mains and grid voltage (230/400 V installations, distribution and transmission networks, substations, generators, protection relays and their tests) is taught here by calculation and simulation only, in Python and ngspice, with the browser labs. Nothing in this course is ever connected to the mains or the grid. The only bench work uses low-voltage analogues: resistor networks and a small DC "grid" fed from a current-limited bench supply of 24 V or less, and AC of 12 V or less from a function generator or a small hand-cranked generator. Arc flash, step and touch voltages and live working are explained as concepts so that you recognise the hazards; working on real equipment needs training, approved instruments and authorisation under the local rules.

The chain from generator to socket

G11-25 kV 400 kV transmission line 132 kV 11-20 kV 230/400 V homes industry =/~solar, wind generationtransmissionsubtransmissiondistribution

The figure is a one-line diagram: each line stands for three phases. Large generators produce at 1111 to 25 kV25\ \text{kV} and a step-up transformer raises this to a transmission voltage such as 400 kV400\ \text{kV}. Grid substations step down to subtransmission (132132 or 110 kV110\ \text{kV}), primary substations to medium-voltage distribution (1111, 2020 or 33 kV33\ \text{kV}), and many small transformers to the 230/400 V230/400\ \text{V} low-voltage network. The voltage levels are the nominal values of IEC 60038 (IEC standard voltages, edition 7.0, 2009, amendment 1 of 2021); Structure and Components gives the full table. Wind farms, solar parks and batteries connect through power-electronic converters at whatever level suits their size.

Why high voltage?

For a given power the current falls in proportion to the voltage, and the resistive loss with its square. That single fact shapes the whole system.

Given: 100 MW100\ \text{MW} delivered at power factor 0.950.95 over 100 km100\ \text{km} of three-phase overhead line with R=0.06 Ω/kmR = 0.06\ \Omega/\text{km} per phase (6 Ω6\ \Omega per phase).

Find: the line current and the loss at 3333, 132132 and 400 kV400\ \text{kV}.

Solve:

I=P3 VLcos⁡ϕ,Ploss=3I2R132 kV:I=100×106 W3⋅132×103 V⋅0.95=460.4 A,Ploss=3⋅(460.4 A)2⋅6 Ω=3.82 MW400 kV:I=151.9 A,Ploss=0.42 MW\begin{aligned} I &= \frac{P}{\sqrt{3}\,V_L \cos\phi}, \qquad P_\text{loss} = 3 I^2 R \\ 132\ \text{kV:}\quad I &= \frac{100 \times 10^6\ \text{W}}{\sqrt{3} \cdot 132 \times 10^3\ \text{V} \cdot 0.95} = 460.4\ \text{A}, \qquad P_\text{loss} = 3 \cdot (460.4\ \text{A})^2 \cdot 6\ \Omega = 3.82\ \text{MW} \\ 400\ \text{kV:}\quad I &= 151.9\ \text{A}, \qquad P_\text{loss} = 0.42\ \text{MW} \end{aligned}

At 33 kV33\ \text{kV} the current would be 1842 A1842\ \text{A} and the loss 61 MW61\ \text{MW}, which is absurd: no one sends 100 MW100\ \text{MW} over 100 km100\ \text{km} at medium voltage.

Check: the loss scales as 1/V21/V^2: (400/132)2=9.18(400/132)^2 = 9.18 and 3.82/0.416=9.183.82/0.416 = 9.18. The same factor limits the voltage drop, which is why long distances need high voltage and why the last few hundred metres to a house can be at 400 V400\ \text{V}.

python · try it yourself
import numpy as np

P, pf, R = 100e6, 0.95, 0.06 * 100          # W, -, ohm per phase over 100 km
for VL in (33e3, 132e3, 400e3):
    I = P / (np.sqrt(3) * VL * pf)
    loss = 3 * I**2 * R
    print(f"{VL/1e3:5.0f} kV: I = {I:7.1f} A, loss = {loss/1e6:6.2f} MW ({100*loss/P:5.1f} % of P)")
print(f"ratio of losses 132/400 kV: {(400/132)**2:.2f}")
   33 kV: I =  1841.6 A, loss =  61.05 MW ( 61.0 % of P)
  132 kV: I =   460.4 A, loss =   3.82 MW (  3.8 % of P)
  400 kV: I =   151.9 A, loss =   0.42 MW (  0.4 % of P)
ratio of losses 132/400 kV: 9.18

Higher voltage costs taller towers, longer insulator strings and bigger clearances, so each level is an economic compromise. Transformers make changing level cheap and efficient, and that is the main reason the world's grids are AC. HVDC links win where AC struggles: very long overhead lines (roughly beyond 600600 to 800 km800\ \text{km}), submarine and underground cables longer than a few tens of kilometres (cable capacitance makes long AC cables draw huge charging currents), and connections between grids that are not synchronous. These break-even distances are rough industry rules of thumb that depend on prices; HVDC and FACTS explains them.

The mains waveform

The lab shows the 230 V230\ \text{V}, 50 Hz50\ \text{Hz} waveform that the whole chain delivers: peak 325 V325\ \text{V}, period 20 ms20\ \text{ms} (slowed 100100 times in the animation); across a 100 Ω100\ \Omega resistor it would dissipate 2302/100=529 W230^2/100 = 529\ \text{W}. Every generator in a synchronous area holds this frequency together; a deviation of a few hundred millihertz is already a serious event (Frequency Control).

U0rotating phasoru (V)tUrms = 230 V325−325T = 20 msp = u²/R (W)average P = 529 W10580R = 100 Ωi = 0.0 Aslow motion:1 s here = 10 ms

The map of the course

Section You will be able to Labs and tools
Getting started read one-line diagrams, voltage levels, substations, lines and cables figures
Three-phase systems and power solve balanced and unbalanced networks per phase and in full, measure three-phase power, correct power factor, work in per unit across several voltage levels ee-three-phase, ee-phasor-diagram, ee-netlist, NumPy
Generation compare thermal, hydro and nuclear plant, run a generator on the grid, compute wind and PV output, storage, capacity factor and LCOE Python, ee-netlist
Transmission lines find R, L and C from geometry, model short, medium and long lines, explain surge impedance loading and the Ferranti effect NumPy, ngspice, ee-netlist
Reactive power and voltage control relate P to angle and Q to voltage, size tap changers and shunt compensation Python, ee-netlist
Load flow build the Y-bus and solve Gauss–Seidel, Newton–Raphson and DC load flows NumPy
Economic operation dispatch generators at equal incremental cost, commit units over a day NumPy, SciPy
Faults compute symmetrical and unsymmetrical fault currents with Thevenin, the Z-bus and symmetrical components, to IEC 60909 NumPy, ngspice, ee-netlist
Protection choose fuses, set IDMT relays and grade them, set distance zones and differential relays, design earthing Python, Matplotlib, ee-transmission-line
Stability integrate the swing equation, apply equal-area, model frequency and voltage stability SciPy solve_ivp, ee-pid-loop
Distribution and power quality compute feeder voltage drop and losses, assess harmonics, flicker and sags Python
The modern grid explain HVDC, FACTS, DER integration to IEEE 1547-2018, microgrids and markets Python

The course builds on Circuit Theory, in particular Complex Power and Three-Phase Circuits, and on Electrical Machines for transformers, synchronous machines and per-unit values. Lines as travelling waves come from Electromagnetic Theory, control loops from Control Systems, and power and harmonic measurement from Measurements. Inverters and converters are the subject of Power Electronics & Motor Drives.

Conventions in this course

Quantity Symbol
phasor (rms) bold, V\mathbf{V}, I\mathbf{I}; magnitude VV, II
line-to-line and phase voltage VLV_L, VphV_\text{ph}; VL=3 VphV_L = \sqrt{3}\,V_\text{ph}
complex power S=P+jQ=VI∗\mathbf{S} = P + jQ = \mathbf{V}\mathbf{I}^* (lagging Q positive)
per-unit value the unit "pu"; system base Sb=100 MVAS_b = 100\ \text{MVA} unless stated
power injected at bus ii Si=(PGi−PDi)+j(QGi−QDi)S_i = (P_{Gi} - P_{Di}) + j(Q_{Gi} - Q_{Di}) (generation positive)
symmetrical-components operator a=1∠120∘a = 1\angle 120^\circ
frequency 50 Hz50\ \text{Hz} unless stated

The running examples are a four-bus 132 kV132\ \text{kV} network N4 (load flow, dispatch), a power station P1 of one 100 MVA100\ \text{MVA} generator, its step-up transformer and a double-circuit line to the grid (faults, stability), an 11 kV11\ \text{kV} distribution feeder F11, and a factory's low-voltage board B1 behind a 1000 kVA1000\ \text{kVA} transformer (protection, earthing). The mini project at the end puts them together in a small power-system study.

Pitfalls

  • Line or phase? Every voltage in a power-system document is line-to-line unless it says otherwise; per-phase analysis uses phase values.
  • Nominal values are not exact. "400 V" is 3⋅230=398.4 V\sqrt{3} \cdot 230 = 398.4\ \text{V}, and the real supply may differ from nominal by several percent.
  • Calculation is not commissioning. A study tells you what to expect; testing real plant is work for authorised people with rated equipment.

Practice

  1. Repeat the loss calculation for 220 kV220\ \text{kV}.
  2. A 20 kV20\ \text{kV} feeder carries 8 MW8\ \text{MW} at pf 0.90.9. What line current flows?
  3. Why can a long submarine link not simply be an AC cable?
Answer
  1. I=100×106/(3⋅220×103⋅0.95)=276.2 AI = 100 \times 10^6/(\sqrt{3} \cdot 220 \times 10^3 \cdot 0.95) = 276.2\ \text{A}, loss =3⋅276.22⋅6=1.37 MW= 3 \cdot 276.2^2 \cdot 6 = 1.37\ \text{MW} (1.4 %).
  2. I=8×106/(3⋅20 000⋅0.9)=256.6 AI = 8 \times 10^6/(\sqrt{3} \cdot 20\,000 \cdot 0.9) = 256.6\ \text{A}.
  3. A cable's capacitance is far larger than an overhead line's, so a long AC cable needs a large charging current at every point. Over some tens of kilometres that current uses up the cable's whole current rating before any power is delivered. DC has no charging current in steady state.

Test yourself

Doubling the transmission voltage at the same power and line resistance changes the I2RI^2R loss by a factor of…

  1. 2
  2. 1/2
  3. 1/4
  4. 4

Which is the main reason most grids are AC rather than DC?

  1. AC has no losses
  2. Transformers change AC voltage cheaply and efficiently
  3. AC lines have no inductance
  4. Generators cannot produce DC

In a one-line diagram, one line stands for…

  1. the neutral
  2. one phase
  3. all three phases
  4. the earth conductor

The nominal 230/400 V low-voltage system in Europe is defined in…

  1. IEC 60909
  2. IEC 60038
  3. IEEE 519
  4. IEC 60255-151