An unloaded 132 kV132\ \text{kV} overhead line 100 km100\ \text{km} long still draws about 22 A22\ \text{A} per phase from the substation, and a 132 kV132\ \text{kV} underground cable draws that much every 5 km5\ \text{km}. That charging current flows through the line's shunt capacitance, and it decides how long an AC cable can be, why lightly loaded lines raise their own voltage (Ferranti Effect), and how much reactive compensation a network needs. This lesson computes the capacitance of overhead lines from their geometry, explains bundling and transposition, and contrasts overhead lines with cables. Electrostatics of conductors is in Capacitance.

Safety: a disconnected line or cable can hold a dangerous charge and can pick up voltage from parallel energised circuits. Only authorised staff earth and test them. This lesson is calculation and simulation only.

Capacitance of a three-phase line

The potential at distance DD from a long line charge qq per metre, relative to its surface at radius rr, is (q/2πε0)ln⁡(D/r)(q/2\pi\varepsilon_0)\ln(D/r). Superposing the three phase charges of a transposed line (charges summing to zero) gives the capacitance from each phase to neutral:

Cn=2πε0ln⁡(GMD/r)  F/m,B=ωCn,Ich=VL3 ωCn ℓ,Qch=VL2 ωCn ℓC_n = \frac{2\pi\varepsilon_0}{\ln(\text{GMD}/r)}\ \ \text{F/m}, \qquad B = \omega C_n, \qquad I_\text{ch} = \frac{V_L}{\sqrt{3}}\,\omega C_n\,\ell, \qquad Q_\text{ch} = V_L^2\,\omega C_n\,\ell

Two differences from the inductance formula of Line Resistance and Inductance:

  • the physical radius rr appears, not the GMR (charge sits on the surface, there is no internal "flux" term);
  • CC is inversely proportional to the same kind of logarithm, so LC≈μ0ε0=1/c2LC \approx \mu_0\varepsilon_0 = 1/c^2: waves on an overhead line travel at nearly the speed of light, and the surge impedance L/C\sqrt{L/C} is about 300300 to 400 Ω400\ \Omega (Long Lines).

The earth beneath the line raises the capacitance slightly; the method of images handles it, and for normal heights the correction is a few percent.

Bundles and transposition

Bundling. For a bundle of nn sub-conductors of radius rr on a circle with spacing dd, the effective radius for capacitance is rd\sqrt{rd} for two, rd23\sqrt[3]{rd^2} for three and 1.09rd341.09\sqrt[4]{rd^3} for four sub-conductors. A bundle therefore has more capacitance and less inductance than a single conductor of the same total area, which raises the line's natural loading. Above all, a bundle lowers the electric field at the conductor surface; at EHV a single conductor would exceed the corona onset field (roughly 22 to 3 MV/m3\ \text{MV/m} at the surface in fair weather, depending on surface condition and air density), causing losses, radio noise and audible hum.

Transposition. In a flat or vertical arrangement the middle phase sees different distances from the outer ones, so the three phases would have different LL and CC. Swapping the positions at towers every third of the line (a transposition cycle) makes each phase occupy each position for one third of the length, so the line is balanced on average and the GMD formula is exact. Untransposed lines create unbalanced voltages and negative-sequence currents, usually tolerated only on short lines.

abc section 1 (l/3)section 2 (l/3)section 3 (l/3) transposition towers

Cables

A single-core cable with a metallic screen is a coaxial capacitor: conductor of radius rr, insulation of relative permittivity εr\varepsilon_r out to radius RR:

C=2πε0εrln⁡(R/r)C = \frac{2\pi\varepsilon_0\varepsilon_r}{\ln(R/r)}

The insulation is thin and εr\varepsilon_r is 2.32.3 to 2.52.5 for XLPE, so a cable has 1515 to 3030 times the capacitance per km of an overhead line, and its series inductance is lower because the phases are close together. Charging current therefore limits AC cable length: at some critical length the charging current alone equals the conductor rating, leaving no capacity for load. Long cables need shunt reactors at the ends (and sometimes in between) or HVDC (HVDC and FACTS). The cable screen must be earthed; screen currents and their losses are managed by bonding schemes (single-point, both-ends, cross-bonding).

Worked example: line and cable charging

Given: the 132 kV132\ \text{kV} line of the previous lesson (conductor radius 12.5 mm12.5\ \text{mm}, GMD 5.04 m5.04\ \text{m}); a 132 kV132\ \text{kV} XLPE cable with conductor radius 17 mm17\ \text{mm}, insulation outer radius 35 mm35\ \text{mm}, εr=2.5\varepsilon_r = 2.5, current rating 800 A800\ \text{A}.

Find: capacitance per km, charging current and reactive power per km for each, and the cable's critical length.

Solve:

Cline=2π⋅8.854×10−12ln⁡(5.04/0.0125)=9.27 nF/km,Ich=132 kV3⋅2π⋅50⋅9.27×10−9=0.222 A/kmCcable=2π⋅8.854×10−12⋅2.5ln⁡(35/17)=193 nF/km,Ich=4.61 A/km,Q=1.05 Mvar/kmℓcrit=800 A4.61 A/km=173 km\begin{aligned} C_\text{line} &= \frac{2\pi \cdot 8.854 \times 10^{-12}}{\ln(5.04/0.0125)} = 9.27\ \text{nF/km}, \qquad I_\text{ch} = \frac{132\ \text{kV}}{\sqrt{3}} \cdot 2\pi \cdot 50 \cdot 9.27 \times 10^{-9} = 0.222\ \text{A/km} \\ C_\text{cable} &= \frac{2\pi \cdot 8.854 \times 10^{-12} \cdot 2.5}{\ln(35/17)} = 193\ \text{nF/km}, \qquad I_\text{ch} = 4.61\ \text{A/km}, \qquad Q = 1.05\ \text{Mvar/km} \\ \ell_\text{crit} &= \frac{800\ \text{A}}{4.61\ \text{A/km}} = 173\ \text{km} \end{aligned}

Check: the cable has 20.820.8 times the capacitance of the line. In practice the useful AC cable length at 132 kV132\ \text{kV} is far shorter than 173 km173\ \text{km} (often a few tens of km without compensation), because the charging current adds to the load current, and voltage rise at the open end and losses also limit it.

python · try it yourself
import numpy as np

e0, w = 8.854e-12, 2 * np.pi * 50
VL = 132e3

C_line = 2 * np.pi * e0 / np.log(5.04 / 0.0125)          # F/m
C_cable = 2 * np.pi * e0 * 2.5 / np.log(35 / 17)
for name, C in (("overhead line", C_line), ("XLPE cable", C_cable)):
    Ich = VL / np.sqrt(3) * w * C * 1e3                   # A per km
    Q = VL**2 * w * C * 1e3                               # var per km
    print(f"{name:13s}: C = {C*1e12:7.2f} nF/km, B = {w*C*1e9:6.3f} uS/km, Ich = {Ich:.3f} A/km, Q = {Q/1e6:.4f} Mvar/km")
print(f"cable/line capacitance ratio: {C_cable / C_line:.1f}")
print(f"critical length at 800 A: {800 / (VL/np.sqrt(3) * w * C_cable * 1e3):.0f} km")

# A 400 kV line: single conductor vs a 2-bundle (r = 12.5 mm, spacing 400 mm), phases 11 m apart in a row
gmd = (11 * 11 * 22) ** (1 / 3)
for label, req in (("single conductor", 0.0125), ("2-bundle", np.sqrt(0.0125 * 0.4))):
    C = 2 * np.pi * e0 / np.log(gmd / req)
    print(f"400 kV {label}: C = {C*1e12:.2f} nF/km, charging {400e3**2 * w * C * 1e3 / 1e6:.3f} Mvar/km")
print(f"LC for the 132 kV line gives v = {1/np.sqrt(1.2425e-6 * C_line):.3e} m/s (c = 2.998e8)")
overhead line: C =    9.27 nF/km, B =  2.913 uS/km, Ich = 0.222 A/km, Q = 0.0508 Mvar/km
XLPE cable   : C =  192.59 nF/km, B = 60.505 uS/km, Ich = 4.611 A/km, Q = 1.0542 Mvar/km
cable/line capacitance ratio: 20.8
critical length at 800 A: 173 km
400 kV single conductor: C = 7.93 nF/km, charging 0.399 Mvar/km
400 kV 2-bundle: C = 10.54 nF/km, charging 0.530 Mvar/km
LC for the 132 kV line gives v = 2.946e+08 m/s (c = 2.998e8)

The wave speed from LL and CC is 98 %98\ \% of cc; the difference is the conductor's internal inductance (GMR instead of rr). Bundling raised the 400 kV400\ \text{kV} line's capacitance by 33 %33\ \%.

Interactive: 20 km of cable, open at the far end

The netlist lab is one phase of 20 km20\ \text{km} of the cable as a nominal π\pi (Short and Medium Lines): 76.21 kV76.21\ \text{kV} phase voltage, R=0.6 ΩR = 0.6\ \Omega, L=8 mHL = 8\ \text{mH} and half the capacitance (1.93 μF1.93\ \mu\text{F}) at each end, with a load resistor RL. Read the values at the 50 Hz50\ \text{Hz} cursor. With the load practically disconnected (1 MΩ1\ \text{M}\Omega) the source supplies 92.49 A92.49\ \text{A} leading by 90∘90^\circ, all of it charging current, and the open end sits at 76.33 kV76.33\ \text{kV}, a little above the source. Slide RL down to see load current add to the charging current.

05000001000000100m1101001k10kf (Hz)|V| (V)0 A5.0 kA10 kA15 kA|I| (A)|V(r)||I(R1)|phasors at f = 50.00 Hz (magnitude @ phase)V(s)76.2 kV @ 0.0 degV(m)76.2 kV @ 0.0 degV(r)76.3 kV @ 0.0 degI(V1)92.5 A @ -90.1 degI(C1)46.2 A @ 90.0 degI(R1)46.3 A @ 89.9 degI(L1)46.3 A @ 89.9 degI(C2)46.3 A @ 90.0 degI(RL)76.3 mA @ 0.0 deg

Guided lab: the capacitance of coaxial cable

Hand calculation. RG-58 coaxial cable has an inner conductor radius of about 0.45 mm0.45\ \text{mm}, a dielectric (polyethylene, εr=2.25\varepsilon_r = 2.25) to about 1.47 mm1.47\ \text{mm}: C=2πε0⋅2.25/ln⁡(1.47/0.45)=106 pF/mC = 2\pi\varepsilon_0 \cdot 2.25/\ln(1.47/0.45) = 106\ \text{pF/m}, close to its datasheet value of about 100 pF/m100\ \text{pF/m}.

Simulation. Change the radii and εr\varepsilon_r in the cable formula of the program.

What you would measure. With an LCR meter at 1 kHz1\ \text{kHz} on 5 m5\ \text{m} and 10 m10\ \text{m} lengths (far end open), expect about 0.50.5 and 1.0 nF1.0\ \text{nF}; the difference between the two removes the meter-lead capacitance. Agreement with the formula within 5 %5\ \% is typical; the radii are the main uncertainty.

Hazards and safe setup. Low-voltage LCR meter only; never test cable insulation with a high-voltage insulation tester without training.

Pitfalls

  • GMR in the capacitance formula. Capacitance uses the physical radius (or the bundle's rd\sqrt{rd} built from it).
  • Line-to-line versus line-to-neutral capacitance. Per-phase models use the capacitance to neutral.
  • Assuming cables behave like lines. Their charging current can dominate; always check it.
  • Ignoring charging current in protection. On long cables it can look like a fault current to differential protection unless compensated.

Practice

  1. A 220 kV220\ \text{kV} line has C=9 nF/kmC = 9\ \text{nF/km}. Find its charging reactive power for 150 km150\ \text{km}.
  2. What capacitance per km has a cable with r=10 mmr = 10\ \text{mm}, R=22 mmR = 22\ \text{mm}, εr=2.4\varepsilon_r = 2.4?
  3. Why do long AC submarine cables need shunt reactors?
Answer
  1. Q=(220×103)2⋅2π⋅50⋅9×10−9⋅150=20.5 MvarQ = (220 \times 10^3)^2 \cdot 2\pi \cdot 50 \cdot 9 \times 10^{-9} \cdot 150 = 20.5\ \text{Mvar}.
  2. C=2π⋅8.854×10−12⋅2.4/ln⁡2.2=169 nF/kmC = 2\pi \cdot 8.854 \times 10^{-12} \cdot 2.4/\ln 2.2 = 169\ \text{nF/km}.
  3. Their charging current is large; reactors absorb that reactive power, freeing the cable's current rating for load and holding down the voltage at the open end.

Test yourself

The capacitance formula of an overhead line uses…

  1. the GMR
  2. the physical conductor radius
  3. the bundle spacing only
  4. the earth resistivity

Compared with an overhead line, an XLPE cable at the same voltage has a capacitance per km about…

  1. the same
  2. half
  3. 15 to 30 times higher
  4. 1000 times higher

Why are lines transposed?

  1. to raise their rating
  2. to balance the three phases' inductance and capacitance
  3. to reduce corona
  4. to allow higher voltage

A cable draws 5 A/km of charging current and is rated 600 A. Its critical length is…

  1. 30 km
  2. 60 km
  3. 120 km
  4. 3000 km